Sign In | Join Free | My carsrow.com |
|
Brand Name : ANGES
Model Number : ACK-60(F)
Place of Origin : China
MOQ : 1
Price : Negotiation
Payment Terms : T/T, L/C
Supply Ability : 400 units/ month
Delivery Time : 10-35 days
Packaging Details : Plywood case
Type : Air Cooled Type
Capacity : 60HP
Compressor typetype : Danfoss/Panosonic/Copeland
Refrigerant : R410a/R407C/R134A/R22
Pump : Included 2 bar- 4 bar
Water tank : 345L
Voltage : 3PH~220V/380/415V~50HZ/60HZ
Dimension(l*w*h) : 2700*2200*2050
Weight : 1850kg
Temperature range : 5℃ ~ 35℃
Application : Industrial Cooling Solutions,Plastic & rubber / Chemical etc / Welding
60ton Air Cooled Industrial Water Chiller for injection molding Machine
The chiller has become an indispensable auxiliary equipment in the injection molding process through precise temperature control and efficient heat dissipation, directly improving production efficiency, product quality and economic benefits.
Choosing a suitable chiller can further optimize the production process and achieve cost reduction and efficiency improvement.
Specification
Item Model | ACK-60F | |
Nominal cooling capacity | Kcal/h | 158928 |
kw | 184.8 | |
Input power | kw | 57.48 |
Power supply | 3PH 380V 50HZ | |
Refrigerant | Type | R22 |
Type of control | Expansion valve | |
Compressor | Type | Hermetic scroll |
Power(kw) | 49.8 | |
Condenser | Type | Finned copper tube + low noise outer rotor fan |
Power(kw) | 3.68 | |
Cooling air flow(m3/h) | 60000 | |
Evaporator | Type | Shell and tube |
Min Chilled fluid flow(m3/h) | 31.86 | |
Inlet/outlet pipe caliber(inch) | 3 | |
Water tank | Volume(L) | 345 |
Pump | Power(kw) | 4 |
Flow(m3/h) | 42 | |
Lift(m) | 21 | |
safety protection | compressor over temperature protection, over load protection, high and low pressure protection, flow switch protection, reversed and lacking phase protection, anti-freezing protection,fusible protection. | |
Weight | kg | 2260 |
Dimension | mm | 3400*2000*2053 |
The main role of the chiller for the injection molding machine
1.Shorten the molding cycle
Quickly take away the heat from the mold, accelerate the solidification of the plastic, and reduce the cooling time of a single product, thereby improving production efficiency.
2.Adapt to different material requirements
Flexibly adjust the water temperature and optimize material properties according to the cooling requirements of different plastics (such as ABS, PC, PP, etc.).
3.Protect molds and equipment
Prevent deformation or thermal fatigue of the mold due to long-term high-temperature operation and extend its service life.
4.Maintain production stability
Avoid shutdown of the injection molding machine due to overheating and ensure the stability of continuous production.
THE AFTER-SALE SERVICE OF ANGES CHILLER!
FAQ
1.How does a chiller system work?
Chiller has two circulation,one is process water circulation,the other is refrigerant gas circulation.Heat picked up from the process.Heat transfers to refrigerant circulation.Heat is remove to air or water.
2.How to calculate cooling capacity for chillers?
Cooling Capacity(kw)= Flow Rate(m3/h)*Temp Change(T1-t2)/0.86
Heat Load= C(specific heat)* M(quality output per hour )*Temp Change(T1-T2)
3.How can we do for chiller maintenance ?
Step 1: Keep Tubes Clean
Step 2: Ensure a Leak-free Unit
Step 3: Sustain Proper Water Treatment(prevent scale, corrosion)
Step 4: Analyze Oil and Refrigerant
![]() |
345L Water Tank 60 Ton Air Cooled Industrial Water Chiller for Injection Molding Machine 2700*2200*2050 Images |